{"paper":{"title":"Fractional Order Modeling of a PHWR Under Step-Back Condition and Control of Its Global Power with a Robust PI{\\lambda}D{\\mu} Controller","license":"http://arxiv.org/licenses/nonexclusive-distrib/1.0/","headline":"","cross_cats":[],"primary_cat":"cs.SY","authors_text":"Amitava Gupta, Saptarshi Das, Shantanu Das","submitted_at":"2012-02-25T19:11:59Z","abstract_excerpt":"Bulk reduction of reactor power within a small finite time interval under abnormal conditions is referred to as step-back. In this paper, a 500MWe Canadian Deuterium Uranium (CANDU) type Pressurized Heavy Water Reactor (PHWR) is modeled using few variants of Least Square Estimator (LSE) from practical test data under a control rod drop scenario in order to design a control system to achieve a dead-beat response during a stepped reduction of its global power. A new fractional order (FO) model reduction technique is attempted which increases the parametric robustness of the control loop due to l"},"claims":{"count":0,"items":[],"snapshot_sha256":"258153158e38e3291e3d48162225fcdb2d5a3ed65a07baac614ab91432fd4f57"},"source":{"id":"1202.5684","kind":"arxiv","version":1},"verdict":{"id":null,"model_set":{},"created_at":null,"strongest_claim":"","one_line_summary":"","pipeline_version":null,"weakest_assumption":"","pith_extraction_headline":""},"references":{"count":0,"sample":[],"resolved_work":0,"snapshot_sha256":"258153158e38e3291e3d48162225fcdb2d5a3ed65a07baac614ab91432fd4f57","internal_anchors":0},"formal_canon":{"evidence_count":0,"snapshot_sha256":"258153158e38e3291e3d48162225fcdb2d5a3ed65a07baac614ab91432fd4f57"},"author_claims":{"count":0,"strong_count":0,"snapshot_sha256":"258153158e38e3291e3d48162225fcdb2d5a3ed65a07baac614ab91432fd4f57"},"builder_version":"pith-number-builder-2026-05-17-v1"}