Evaluating Grid Resilience in the Era of Ever-Increasing Data Centers
Replacing a conventional load with energy-matched and scaled data center demand at a contingency-exposed bus in an IEEE 30-bus system increases unserved energy under transmission-constrained contingencies, with disruption-coincident demand amplifying the effect by 34.4%.