Switching Transients in Constrained Transformer-Line/Cable Configurations
Not yet reviewed by Pith; the record is open.
This paper has not been read by Pith yet. Machine review is queued; the pith claim, tier, and objections will appear here once it completes.
SPECIMEN: schema-true, not a live event
T0 review · schema-true
One-sentence machine reading of the paper's core claim.
pith:XXXXXXXX · record.json · timestamp
read the original abstract
This paper investigates the transient phenomena that occur in two special cases in the Netherlands: (A) during the energization of a power transformer via a cable feeder and (B) the energization of a power transformer together with an overhead line (OHL). In Case A a 7 km long 150 kV cable and a 150/50 kV transformer are connected and energized at the same time. In Case B a 150/50 kV transformer and a short 50 kV OHL are connected and energized simultaneously. The reason behind this kind of situations is related to space restrictions and cost efficiency.