Pith. sign in

REVIEW

Identifying Oscillations Injected by Inverter-Based Solar Energy Sources

Not yet reviewed by Pith; the record is open.

This paper has not been read by Pith yet. Machine review is queued; the pith claim, tier, and objections will appear here once it completes.

SPECIMEN: schema-true, not a live event

T0 review · schema-true

One-sentence machine reading of the paper's core claim.

pith:XXXXXXXX · record.json · timestamp

arxiv 2202.11579 v1 pith:26VI6ZN7 submitted 2022-02-23 eess.SP

classification eess.SP
keywords energyanalysismodedominionfrequencyinverter-basedsolarsources
verification ladder T0 review T1 audit T2 compute T3 formal
0 comments
read the original abstract

Inverter-based solar energy sources are becoming widely integrated into modern power systems. However, their impacts on the system in the frequency domain are rarely investigated at a higher frequency range than conventional electromechanical oscillations. This paper presents evidence of the emergence of an oscillation mode injected by inverter-based solar energy sources in Dominion Energy's service territory. This new mode was recognized from the analysis of real-world ambient synchrophasor and point-of-wave data. The analysis was performed by developing customized synchrophasor analysis tools deployed on the PredictiveGrid^{TM} platform implemented at Dominion Energy. Herein, we describe and illustrate the preliminary analysis results acquired from spectrogram observations, power spectral density plots, and mode shape estimation. The emergence and propagation of this new mode in Dominion Energy's footprint is illustrated using a heatmap based on a proposed frequency component energy metric, which helps to assess this oscillation's spread and impact.

Discussion (0). Continue with ORCID to comment.

Pith tools