Degradation-aware data-enabled predictive control of energy hubs

Reviewed by Pithpith:XDNXTQZ4open to challenge →

classification eess.SY cs.SY
keywords energybuildingcontrolbatterydeepccomfortcontrollerdata-enabled
0
0 comments X
read the original abstract

Mitigating the energy use in buildings, together with satisfaction of comfort requirements are the main objectives of efficient building control systems. Augmenting building energy systems with batteries can improve the energy use of a building, while posing the challenge of considering battery degradation during control operation. We demonstrate the performance of a data-enabled predictive control (DeePC) approach applied to a single multi-zone building and an energy hub comprising an electric heat pump and a battery. In a comparison with a standard rule-based controller, results demonstrate that the performance of DeePC is superior in terms of satisfaction of comfort constraints without increasing grid power consumption. Moreover, DeePC achieved two-fold decrease in battery degradation over one year, as compared to a rule-based controller.