pith. sign in

arxiv: 1308.5474 · v2 · pith:SUWTI3QPnew · submitted 2013-08-26 · 🧮 math.OC · physics.soc-ph

Changes in Cascading Failure Risk with Generator Dispatch Method and System Load Level

classification 🧮 math.OC physics.soc-ph
keywords riskblackoutcascadingfailuredispatchlevelloadsystem
0
0 comments X
read the original abstract

Industry reliability rules increasingly require utilities to study and mitigate cascading failure risk in their system. Motivated by this, this paper describes how cascading failure risk, in terms of expected blackout size, varies with power system load level and pre-contingency dispatch. We used Monte Carlo sampling of random branch outages to generate contingencies, and a model of cascading failure to estimate blackout sizes. The risk associated with different blackout sizes was separately estimated in order to separate small, medium, and large blackout risk. Results from $N-1$ secure models of the IEEE RTS case and a 2383 bus case indicate that blackout risk does not always increase with load level monotonically, particularly for large blackout risk. The results also show that risk is highly dependent on the method used for generator dispatch. Minimum cost methods of dispatch can result in larger long distance power transfers, which can increase cascading failure risk.

This paper has not been read by Pith yet.

discussion (0)

Sign in with ORCID, Apple, or X to comment. Anyone can read and Pith papers without signing in.