Data Center Cooling System Optimization Using Offline Reinforcement Learning

Not yet reviewed by Pith; the record is open.

This paper has not been read by Pith yet. Machine review is queued; the pith claim, tier, and objections will appear here once it completes.

SPECIMEN: schema-true, not a live event

T0 review · schema-true

One-sentence machine reading of the paper's core claim.

pith:XXXXXXXX · record.json · timestamp

arxiv 2501.15085 v2 pith:7NY4XX4W submitted 2025-01-25 cs.AI cs.LGcs.SYeess.SY

classification cs.AIcs.LGcs.SYeess.SY
keywords coolingdataofflinecontrolenergyframeworklearninglimited
verification ladder T0 review T1 audit T2 compute T3 formal
0 comments
read the original abstract

The recent advances in information technology and artificial intelligence have fueled a rapid expansion of the data center (DC) industry worldwide, accompanied by an immense appetite for electricity to power the DCs. In a typical DC, around 30~40% of the energy is spent on the cooling system rather than on computer servers, posing a pressing need for developing new energy-saving optimization technologies for DC cooling systems. However, optimizing such real-world industrial systems faces numerous challenges, including but not limited to a lack of reliable simulation environments, limited historical data, and stringent safety and control robustness requirements. In this work, we present a novel physics-informed offline reinforcement learning (RL) framework for energy efficiency optimization of DC cooling systems. The proposed framework models the complex dynamical patterns and physical dependencies inside a server room using a purposely designed graph neural network architecture that is compliant with the fundamental time-reversal symmetry. Because of its well-behaved and generalizable state-action representations, the model enables sample-efficient and robust latent space offline policy learning using limited real-world operational data. Our framework has been successfully deployed and verified in a large-scale production DC for closed-loop control of its air-cooling units (ACUs). We conducted a total of 2000 hours of short and long-term experiments in the production DC environment. The results show that our method achieves 14~21% energy savings in the DC cooling system, without any violation of the safety or operational constraints. Our results have demonstrated the significant potential of offline RL in solving a broad range of data-limited, safety-critical real-world industrial control problems.

Discussion (0). Sign in to comment.

Forward citations

Cited by 1 Pith paper

Reviewed papers in the Pith corpus that reference this work. Sorted by Pith novelty score.

  1. Dual-Loop Control in DCVerse: Advancing Reliable Deployment of AI in Data Centers via Digital Twins

    cs.AI 2026-04 unverdicted novelty 4.0 of 10

    The Dual-Loop Control Framework uses digital twins and a reservoir of DRL agents to enable safer deployment of AI for data center cooling, delivering up to 4.09% energy savings in real-world case studies without viola...

Pith tools