Electricity Price-Aware Scheduling of Data Center Cooling

classification math.OC
keywords coolingelectricitydatacentercostsmodelgridprice-aware
verification ladder T0 review T1 audit T2 compute T3 formal T4 reserved
0 comments
read the original abstract

Data centers are becoming a major consumer of electricity on the grid, with cooling accounting for about 40\% of that energy. As electricity prices vary throughout the day and year, there is a need for cooling strategies that adapt to these fluctuations to reduce data center cooling costs. In this paper, we present a model for electricity price-aware cooling scheduling using a Markov Decision Process(MDP) framework to reliably estimate the cooling system operational costs and facilitate investment-phase decision-making. We utilize Quantile Fourier Regression (QFR) fits to classify electricity prices into different regimes while capturing both daily and seasonal patterns. We simulate 14 years of operation using historical electricity price and outdoor temperature data, and compare our model against heuristic baselines. The results demonstrate that our approach consistently achieves lower cooling costs. This model is useful for grid operators interested in demand response programs and data center investors looking to make investment decisions.

discussion (0)

Sign in with ORCID, Apple, or X to comment. Anyone can read and Pith papers without signing in.